Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the morenews domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/jobsdqct/eeediary.com/wp-includes/functions.php on line 6121
What is the significance of Protected Unit Scaling Factor in relay setting calculation? - eeediary.com
Site icon eeediary.com

What is the significance of Protected Unit Scaling Factor in relay setting calculation?

For Relay setting of any protected unit like HT Motor, it required FLC, CT Primary and secondary and Relay input current.

In almost cases,FLC and CT Primary current never matched.yes, CT secondary and Rated Relay input current are matched.

That’s are like 1000/5 A 930 A or 2000/5 A 1650 A consider, Rated Relay input current is 5A.

So, Protected unit scaling factor =

1000 5

——-X —– = 1.21

5 930

means, when Relay sense 1 A current,that time protected unit will be running at 1.21 times of FLC.

So, Protected unit scaling factor is a multiplication factor used to bridge the gap between FLC and Rated CT Primary current duringRelay setting calculations.

hence, Per unit scaling factor=

CT Py current * Rated Relay current

————— X ———————–

CT Sy current FLC

Smart Motor Protection Relays are automatically calculating this factor after putting all relevant datas.